NEN 1010 §531.3

Background Leakage Current (Cumulative Leakage — Large Installation)

Achtergrondlekstroom (cumulatieve lekstroom grote installatie)

The sum of the small, normal leakage currents to earth continuously produced by each individual device fitted with an EMC suppression filter (variable frequency drives, IT equipment, LED drivers, switch-mode power supplies), which, with a large number of devices connected within the same installation, can add up to a substantial total leakage current — even without any actual earth fault being present. When this cumulative background leakage current reaches a substantial fraction of the rated residual current of an upstream RCD, it can cause nuisance tripping at the slightest additional leakage current, or reduced sensitivity to genuine earth faults. Control is achieved by spreading leakage current over several selectively switched RCD groups instead of a single central RCD, and by accounting at the design stage for the summed manufacturer-stated leakage current of each connected device.

Practical example

Bij een kantoorpand met honderden IT-werkplekken en meerdere serverkasten met schakelende voedingen kiest de ontwerper voor vier afzonderlijke 100 mA-hoofdaardlekschakelaars per verdieping in plaats van één centrale 300 mA-RCD voor het hele pand, om de cumulatieve achtergrondlekstroom te spreiden en nuisance-uitschakeling te voorkomen.

Common mistake

Bij het uitbreiden van een bestaande groepenkast met extra frequentieregelaars of LED-verlichting geen rekening houden met de reeds aanwezige achtergrondlekstroom van de overige groepen op dezelfde aardlekschakelaar — de optelsom kan de aardlekschakelaar dicht bij de afschakeldrempel brengen, ook zonder een daadwerkelijke fout.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Background Leakage Current (Cumulative Leakage — Large Installation) — dictionary · NEN-Hub