Earthing Grid (Ground Mat) — Substation / HV Yard

Aardingsrooster (aardmat) — onderstation / hoogspanningsterrein

A meshed network of bare copper (or galvanised-steel) conductors laid horizontally underground, usually supplemented with vertical earth rods at the crossing points, installed beneath a substation or HV yard to keep touch and step voltage at grade within permissible limits (IEC 60364-5-54 / IEEE 80) during an earth fault. Mesh spacing and burial depth are calculated from the soil resistivity, the expected fault current and the protection's clearing time: a finer mesh brings the surface potential down towards the remote reference potential faster, but raises material cost. All metal enclosures, fencing and cable trays within the yard are bonded to the grid so that no hazardous potential difference arises between accessible parts.

Practical example

Bij het ontwerp van een nieuw 10/0,4kV-transformatorstation berekent de ontwerper op basis van de gemeten bodemweerstand en de maximale aardfoutstroom de vereiste maaswijdte van het aardingsrooster, en verkleint deze lokaal bij de toegangspoort waar personen met blote voeten of natte schoenen kunnen staan.

Common mistake

Bij een latere uitbreiding van het terrein een nieuw hekwerk of kabelgoot plaatsen zonder deze met het bestaande aardingsrooster te verbinden — hierdoor kan het nieuwe metalen deel op een ander potentiaal komen te staan dan de vermaasde grond eronder, wat juist de gevaarlijke aanraakspanning creëert die het rooster moest voorkomen.