Comparing motor starting methods — DOL, star-delta, soft starter, VFD
Comparing motor starting methods — DOL, star-delta, soft starter, VFD
The motor replacement guide covers how to safely replace a motor, including the star/delta choice on the nameplate. This article covers a different aspect of the same motor: which starting method you choose, and why that directly affects inrush current, starting torque and the stress on cabling and switchgear.
The four common starting methods
| Method | Typical inrush current | Principle |
|---|---|---|
| DOL (direct-on-line) | approx. 5–8× In | Motor gets full mains voltage immediately; simplest, but highest inrush current and shock. |
| Star-delta | approx. 1.5–2× In | Motor starts in star (each winding gets only the phase voltage, 1/√3 of the line voltage) and switches over to delta after a delay for full operation. |
| Soft starter | approx. 2.5–4× In | Thyristors (SCRs) ramp up the voltage gradually over an adjustable ramp time (typically 5–30 s). |
| Variable frequency drive (VFD) | approx. 1–1.5× In | Controls both voltage and frequency from a low level, keeping slip — and therefore current — low while still delivering full torque. |
Note: these are typical orders of magnitude from practice, not guaranteed values for every motor — the actual inrush current depends on the motor design (cage type), the load during starting, and the soft-starter/VFD settings.
Why star-delta isn't always a good alternative
Star-delta reduces inrush current, but the starting torque drops proportionally with it — because torque is approximately proportional to the square of the applied voltage, the star position delivers only about one-third of the DOL starting torque. For a load with high starting torque (for example a fully loaded conveyor or a compressor already under pressure), the motor in star simply may not reach speed — it stays "stuck" until the current rises too high or the motor protection trips. Star-delta is therefore mainly suitable for low-starting-torque loads such as fans and centrifugal pumps that start relatively unloaded.
The switchover moment itself (from star to delta) also causes a brief, sharp current and torque spike because the motor is momentarily de-energised during the switch and then re-energised out of phase — with an incorrectly set switchover time (too early, before the motor has reached sufficient speed) that spike can become just as high as a DOL start.
Soft starter versus variable frequency drive
A soft starter only controls voltage (via phase-angle control with thyristors) and keeps the mains frequency fixed — suitable for limiting inrush current and mechanical shock at start-up, but offers no speed control during operation; after the ramp phase the motor is typically bypassed directly onto the full mains.
A variable frequency drive controls both voltage and frequency simultaneously (V/f ratio), keeping slip — and therefore drawn current — low throughout the entire start while motor torque remains intact. That makes a VFD suitable for applications that also need variable speed during operation (pumps, fans with flow control), but it brings its own consideration: see the frequentieomvormer-aarding-emc guide for the EMC earthing and bearing currents that come with PWM drive control.
Practical relevance
When choosing or replacing a starting method for a three-phase motor, it must be established: what starting torque does the load need (a high starting torque often rules out a simple star-delta start), is variable speed needed during operation (then a VFD), and is the cabling/motor protection (see also the motor replacement guide) rated for the actual inrush current of the chosen method.
Common mistakes
- Applying star-delta to a load with high starting torque — the starting torque in star is only about one-third of the DOL torque; the motor then fails to reach speed.
- Setting the star-to-delta switchover time too short — the motor has not yet reached sufficient speed at switchover, causing a sharp current/torque spike that defeats the intended current limitation.
- Treating a soft starter and a variable frequency drive as interchangeable — a soft starter only controls the starting phase (fixed mains frequency, no speed control during operation), a VFD continuously controls both voltage and frequency.
Related
Further reading
- IEC 61800-3Installing variable-speed drives — EMC grounding and bearing currents (IEC 61800-3)
- PracticalMeasuring Earth Electrode Resistance — 3-Point Method
- PracticalSafely replacing a 3-phase motor — residual energy & Y/Δ
- PracticalUpgrading a connection — the application procedure with the grid operator
- PracticalReading a single-line diagram — the difference with a panel schedule
- PracticalMeasuring instruments and CAT categories — the right instrument for the job