Spring-Charged Operating Mechanism — Power Circuit Breaker
Drive mechanism for opening and closing a power circuit breaker (IEC 62271-100) in which a motor or hand crank charges a closing spring, which then rapidly releases the required energy on a closing command to close the contacts at sufficient making speed, independent of any fluctuations in the auxiliary supply voltage at that moment. A separate opening spring, charged when the breaker closes, provides the energy to open the contacts rapidly on a tripping command (manual or via a protection relay). The mechanism typically has a 'spring charged' indication on the front of the breaker; an uncharged closing spring means the breaker cannot be closed remotely until the spring is recharged, which is relevant when assessing operational readiness during an inspection.
Bij een schakelhandeling in een hoofdverdeelinrichting controleert de VP eerst de 'spring charged'-indicator op de vermogensschakelaar voordat een sluitcommando wordt gegeven, om te garanderen dat de schakelaar met voldoende snelheid sluit.
Een sluitcommando herhaaldelijk geven aan een vermogensschakelaar waarvan de sluitveer niet oplaadt (bijvoorbeeld door een defecte oplaadmotor) — zonder gespannen veer sluit de schakelaar niet of te langzaam, wat tot verhoogde contactslijtage of een mislukte inschakeling onder belasting kan leiden.