NEN-Hub
🔍
NEN-EN 50160

Voltage Characteristics per NEN-EN 50160

Spanningskarakteristieken volgens NEN-EN 50160

NEN-EN 50160 specifies the properties of the voltage a grid operator must supply at the connection point of a low-voltage customer under normal operating conditions: nominal voltage 230/400 V with a permitted deviation typically of plus/minus 10 percent, mains frequency 50 Hz plus/minus 1 percent (99.5 percent of the time), phase-to-phase voltage unbalance of at most 2 percent, and limit values for harmonics (THD), flicker and voltage dips. The standard does not set requirements for the quality of the installation itself but for what the grid operator delivers, and therefore forms the reference framework against which power-quality measurements are assessed.

Practical example

Bij een klacht over knipperende verlichting in een woning plaatst de meetploeg een powerquality-analyzer die een week lang logt en toetst de resultaten aan de grenswaarden van NEN-EN 50160 om vast te stellen of de netbeheerder of de installatie van de klant de oorzaak is.

Common mistake

Denken dat NEN-EN 50160 garandeert dat de spanning altijd binnen de grenzen blijft — de norm staat toe dat de spanning gedurende een klein percentage van de tijd (bv. 5%) buiten de opgegeven marges valt, wat vaak over het hoofd wordt gezien bij het beoordelen van meetresultaten.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Voltage Characteristics per NEN-EN 50160 — dictionary · NEN-Hub