Fault Ride-Through (LVRT/FRT) — Inverter Stays Connected During a Grid Disturbance
A requirement (laid down in NEN-EN 50549-1 and the European grid connection code for generators, EU 2016/631 'NC RfG') that an inverter-connected generating unit (PV, wind, battery) must not trip immediately during a brief grid voltage dip — for example caused by a remote short circuit — but must stay connected and continue actively supporting the grid, as long as the voltage stays within a prescribed voltage-time curve (for example, returning to normal voltage within a few hundred milliseconds to a few seconds). Before fault-ride-through requirements were introduced, inverters would trip en masse and simultaneously at every dip, which actually worsened the original problem — a power deficit — triggering a cascading outage. As the share of inverter-connected generation in the grid grows, compliance with the fault-ride-through curve becomes essential for system stability, and the inverter must additionally inject active reactive current during the dip to support grid voltage ('fast fault current injection').
Bij het certificeren van een nieuwe PV-omvormer voor aansluiting op het Nederlandse net test de fabrikant of de omvormer bij een gesimuleerde spanningsdip tot 0% gedurende 150 ms aangesloten blijft en daarna correct terugkeert naar normaal bedrijf, conform de fault-ride-through-curve van NEN-EN 50549-1.
Bij het in bedrijf stellen van een omvormerpark de fabrieksinstelling voor onder-/overspanningsbeveiliging ongewijzigd laten staan op een te gevoelige (korte) uitschakeltijd, in de veronderstelling dat sneller afschakelen altijd veiliger is — hierdoor voldoet de installatie niet aan de fault-ride-through-eis en kan een op zichzelf onschuldige, kortstondige dip elders in het net alsnog een cascade-uitval van het hele omvormerpark veroorzaken.