Dynamic Resistance Measurement (DRM) — Circuit Breaker Contacts During Switching

Dynamische resistentiemeting (DRM) — contacten vermogensschakelaar tijdens schakelen

A diagnostic measurement technique (recommended by CIGRE WG A3, complementary to IEC 62271-100) that, unlike a static transition-resistance measurement on a stationary, closed breaker, continuously records the resistance of a power circuit breaker's main and arcing contacts during an actual switching operation. Because the resistance profile during opening or closing is captured, mechanical deviations are revealed that a static measurement misses: including contact erosion, incorrect overlap timing between main and arcing contacts, or disturbed magnetic-blowout coil operation, since each of these phenomena produces a characteristic, recognisable pattern in the resistance-versus-time curve.

Practical example

Bij een grootschalige revisie van een 10kV-vermogensschakelaar voert de specialist een DRM-test uit tijdens een testschakeling en herkent in de curve een afwijkende contact-overlaptijd, wat duidt op versleten hoofdcontacten die bij een normale statische meting nog binnen de norm zouden zijn gevallen.

Common mistake

Uitsluitend een statische overgangsweerstandmeting op de gesloten schakelaar uitvoeren en die als volledige contactdiagnose beschouwen — een verkeerde contact-overlaptijd of beginnende boogcontactschade tijdens het schakelen zelf blijft daarmee onopgemerkt, omdat die zich alleen tijdens de dynamische schakelbeweging manifesteert.