IEC 62305-3 / NEN 1010 §542

Earth Resistance — Seasonal Variation (Frost/Drought)

Aardweerstand — seizoensvariatie (vorst/droogte)

A phenomenon whereby the measured earth resistance of an earthing system can vary considerably with the seasons, because soil resistivity depends strongly on moisture content and temperature: frozen ground and very dry ground both have much higher resistivity than moist, unfrozen ground. An earth resistance measurement taken during a wet winter period can therefore give a more favourable (lower) value than the same measurement taken during a dry summer period or during frost, even though the installation itself is unchanged in both cases. For critical applications such as lightning protection (IEC 62305-3), it is therefore advised to take measurements under unfavourable soil conditions, or to maintain a safety margin relative to the limit value, so that the earth resistance still complies even under the worst-case seasonal conditions.

Practical example

Bij de oplevering van een bliksembeveiligingsinstallatie in augustus tijdens een droge periode houdt de installateur rekening met de te verwachten hogere aardweerstand in de winter en kiest een aardingsconfiguratie met voldoende marge onder de norm.

Common mistake

Een aardweerstandmeting slechts één keer uitvoeren, tijdens een gunstig vochtig moment in het jaar, en die waarde als permanent geldig beschouwen — een installatie die in de zomer nog net voldoet, kan in een droge periode of bij vorst boven de toegestane grenswaarde uitkomen.