Zone-Selective Interlocking (ZSI) — Power Circuit Breaker

Zone-selectieve vergrendeling (ZSI) — vermogensschakelaar

A protection function on electronic trip units of power circuit breakers (IEC 60947-2) in which breakers communicate via a wired signal loop to achieve discrimination without the long time delays of classic time-graded discrimination. If a downstream breaker detects a short circuit within its own zone, it sends a restraint signal to the upstream breaker so that the upstream breaker keeps its normal (longer) delay; if the upstream breaker receives no restraint signal — meaning the fault is within its own zone, downstream of that breaker — it trips almost instantaneously. This significantly shortens the effective tripping time for a fault close to the source compared with conventional time grading, without losing discrimination between stages.

Practical example

Bij het ontwerp van een hoofdverdeelinrichting met drie trappen vermogensschakelaars in serie kiest de ontwerper ZSI in plaats van klassieke tijdstaffeling, zodat een kortsluiting direct achter de hoofdschakelaar binnen enkele tientallen milliseconden wordt afgeschakeld in plaats van na de volle, opgetelde staffelingstijd.

Common mistake

ZSI toepassen tussen schakelaars van verschillende fabrikanten zonder te verifiëren of hun trip-units een compatibel ZSI-protocol en dezelfde bedrading ondersteunen — een niet-compatibele koppeling laat de blokkeersignalen wegvallen, waardoor alle schakelaars terugvallen op hun eigen basisvertraging en de bedoelde snelle uitschakeling nabij de bron uitblijft.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Zone-Selective Interlocking (ZSI) — Power Circuit Breaker — dictionary · NEN-Hub