NEN-EN-IEC 62040-3

UPS Classification VFI/VFD/VI (IEC 62040-3)

UPS-classificatie VFI/VFD/VI (IEC 62040-3)

Classification of uninterruptible power supplies (UPS) per NEN-EN-IEC 62040-3 based on how the output voltage behaves under mains variations: VFD (Voltage and Frequency Dependent, "offline/standby") switches over only on mains failure and otherwise passes through largely unconditioned mains power; VI (Voltage Independent, "line-interactive") actively regulates voltage but stays synchronised with the mains; VFI (Voltage and Frequency Independent, "online double-conversion") continuously supplies a sine wave fully generated by the UPS, decoupled from the mains. The correct class is chosen based on the sensitivity of the connected equipment to voltage dips and transfer time.

Practical example

Voor een serverruimte met apparatuur die geen enkele onderbreking verdraagt, kiest de installateur een VFI (online double-conversion) UPS in plaats van een goedkopere VFD-uitvoering, ondanks het lagere rendement van de VFI-variant.

Common mistake

Een goedkope VFD (offline/standby) UPS toepassen voor gevoelige IT- of medische apparatuur omdat "het toch een UPS is" — de omschakeltijd en de doorgegeven netstoringen van een VFD-UPS zijn voor dit soort belasting vaak niet aanvaardbaar.