Sympathetic Tripping (Cascading, Unwanted Protection Operation)
A phenomenon in a meshed or parallel-fed network in which the protection of a healthy feeder that is not affected by the fault incorrectly operates while another, parallel feeder is re-energised after a fault, because the transient (inrush-like) current redistribution occurring when supply is restored temporarily drives a current through the healthy feeder that exceeds the protection setting. This occurs in particular in networks with multiple parallel transformers or cables feeding a common busbar system: once a fault on one feeder has been cleared and it is reconnected, the resulting inrush current can also flow through the unfaulted parallel feeder via magnetic coupling or the shared busbar and cause that feeder's (overcurrent) protection to operate, even though there is no fault on that feeder itself. Sympathetic tripping is avoided by carefully coordinating the settings and time delays of parallel protections and, where necessary, by activating inrush-restraint functions in the relays.
Na het klaren van een kortsluiting op één van twee parallelle 10kV-voedingskabels naar een onderstation merkt de storingsanalist dat bij het terugschakelen van de gerepareerde kabel ook de beveiliging van de andere, ongestoorde kabel kortstondig aanspreekt door de gezamenlijke inrushstroom — een klassiek geval van sympathetic tripping dat om herziening van de tijdcoördinatie vraagt.
Bij het onderzoeken van een onverklaarbare uitschakeling van een schijnbaar gezonde lijn er meteen van uitgaan dat de beveiliging defect is of een fantoomfout heeft gedetecteerd, zonder te controleren of de uitschakeling samenviel met het terugschakelen van een parallelle lijn na een fout — hierdoor blijft het onderliggende coördinatieprobleem (sympathetic tripping) onopgemerkt en kan de storing zich bij een volgende gelegenheid herhalen.