Voltage Transformer (VT) — Accuracy Class and Burden
A measuring transformer that converts a high primary voltage (medium or high voltage) to a standardised low-voltage value (typically 100 V or 110 V) for metering and protection purposes, classified per IEC 61869-3 with an accuracy class (e.g. 0.2 for revenue metering, 0.5 for operational metering, 3P or 6P for protection purposes) that indicates the maximum permissible error in magnitude and phase angle within a specified load range. The burden is the load connected to the secondary side of the VT (meters, relays, wiring), expressed in VA at nominal secondary voltage; the stated accuracy class only applies within the range between the minimum burden (typically 25% of rated burden) and the rated burden itself. A VT loaded with too low a burden (too little connected load) can fall outside the class accuracy due to core saturation or internal voltage drop, while too high a burden (too many meters/relays connected in series) can likewise degrade accuracy or even lead to overheating.
Bij de uitbreiding van een middenspanningsschakelinstallatie met een extra beveiligingsrelais op dezelfde spanningstransformator controleert de ontwerper of de totale aangesloten burden nog binnen het nominale burden-bereik van de VT valt, om de opgegeven nauwkeurigheidsklasse te behouden.
Extra meters of relais op een bestaande VT aansluiten zonder de totale burden opnieuw te berekenen — de VT kan hierdoor buiten zijn nominale burden-bereik gaan werken, met een meetfout tot gevolg die pas bij een facturatiegeschil of een verkeerd werkende beveiliging aan het licht komt.