Under-Frequency Load Shedding (UFLS)

Onderfrequentiebelastingafwerping (UFLS)

A protection scheme (IEC 60255-181, laid down in the Dutch Grid Code) that, during a major power deficit in the electricity network — for example following the loss of a large power station — automatically sheds tiers of load in steps once the grid frequency drops below set thresholds (in the Netherlands typically starting at 49.0 Hz in several steps down to 47.5 Hz). The aim is to prevent the frequency from dropping so far that generators trip themselves for self-protection, which could cause a complete black-out: by timely removing part of the demand, the balance between generation and consumption is restored and the remaining network stays in service. Large consumers and grid operators are required to install relays with UFLS settings at defined shedding stages on connections designated by the grid operator.

Practical example

Een industrieel bedrijf met een grootverbruikersaansluiting installeert op verzoek van de netbeheerder een UFLS-relais dat bij 49,0 Hz automatisch een niet-kritisch deel van de productielijn afschakelt, zodat het bedrijf bijdraagt aan de netstabiliteit tijdens een landelijk vermogenstekort.

Common mistake

De UFLS-afschakeltrappen van een aansluiting zelf instellen op basis van een schatting in plaats van de exacte, door de netbeheerder voorgeschreven frequentiedrempels en tijdvertragingen te gebruiken — een afwijkende instelling kan de gecoördineerde, getrapte afschakeling van het landelijke net verstoren en juist een grotere instabiliteit veroorzaken.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Under-Frequency Load Shedding (UFLS) — dictionary · NEN-Hub