Hipot Test (High-Potential Withstand Test)
A dielectric breakdown test in which a voltage significantly higher than the nominal operating voltage of a switchgear assembly, transformer, cable or other equipment is applied for a short, standardised time (typically 1 minute, sometimes 1 second for a routine test in production), to verify that the insulation can withstand a brief overvoltage without breakdown or flashover. Unlike an insulation resistance measurement with a megohmmeter, which applies a relatively low DC voltage and yields a resistance value in megohms, the hipot test is a pass/fail test at a much higher voltage level (for example 2× Un + 1000 V) that specifically looks for weak spots, air pockets or damaged insulation that would not yet fail at normal operating voltage. The test is applied both as a type/routine test in the factory (NEN-EN 61439-1/2 for low-voltage switchgear and controlgear assemblies) and during commissioning and periodic maintenance of cables and larger machines, using AC or DC voltage depending on the object under test.
Na reparatie van een laagspanningsverdeelinrichting na waterschade voert de fabrikant een hipot-test bij 2,5 kV AC gedurende 1 minuut uit op elke fase-aarde- en fase-fase-combinatie, voordat de kast weer in bedrijf wordt genomen, om verborgen vochtschade aan de isolatie uit te sluiten.
Een hipot-test uitvoeren op apparatuur die elektronische componenten (zoals een frequentieregelaar of een PV-omvormer) bevat zonder deze eerst te ontkoppelen — de hoge testspanning kan gevoelige halfgeleiders onherstelbaar beschadigen, terwijl de isolatie van de bekabeling zelf prima getest had kunnen worden zonder die schade.