IEC 60071-2

Ferroresonance (Voltage Transformer)

Ferroresonantie (spanningstransformator)

A non-linear resonance phenomenon that can occur in medium-voltage networks when the saturable magnetising inductance of a voltage transformer (VT) interacts with the network's capacitance (for example cable capacitance or the capacitance of open circuit-breaker contacts), producing a self-sustaining, strongly distorted and sometimes chaotic voltage and current oscillation that can be significantly higher than rated values. Ferroresonance is often triggered by switching operations such as connecting or disconnecting an isolated (unearthed) star point, switching a lightly loaded or unloaded VT, or the partial closing of a three-pole switch. Consequences range from audible humming and vibration in the VT to overheating, insulation failure or even destruction of the VT due to the sustained overvoltage. Common countermeasures include adding a damping resistor (ferroresonance suppression resistor) in the VT's secondary winding, using electronic VTs that are less susceptible to this phenomenon, or design changes that avoid the critical combination of network capacitance and VT magnetising characteristic.

Practical example

Na het optreden van hoorbaar brommen en een oscillerende spanningsindicatie op een ongeaard middenspanningsnet na het schakelen van een lastarme VT, herkent de storingsmonteur dit als een klassiek geval van ferroresonantie en adviseert een dempweerstand in de secundaire wikkeling.

Common mistake

Een oscillerende of vervormde spanningsindicatie op een VT direct toeschrijven aan een defecte transformator of meetfout, zonder ferroresonantie als mogelijke oorzaak te overwegen — vooral bij recente schakelhandelingen op een geïsoleerd sterpunt of een lastarme VT is ferroresonantie een bekende, herkenbare oorzaak.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Ferroresonance (Voltage Transformer) — dictionary · NEN-Hub