Phasor Meter (Vector / Phase Angle Measurement)

Fasorimeter (vector-/fasehoekmeting)

A measuring instrument that records both the magnitude and the phase angle, relative to a common reference, of every phase voltage and current in a three-phase system and displays these as vectors (phasors) in a vector diagram, unlike a simple phase-sequence monitor that only determines rotation direction (L1-L2-L3 or L1-L3-L2). Phase angle measurement reveals whether voltages and currents are correctly offset relative to one another (nominally 120° in a balanced system) and exposes problems such as a wrongly connected current transformer, unbalanced load or incorrect polarity that would remain unnoticed with amplitude measurements alone. Phasor meters are widely used when commissioning energy meters, protection relays and power analysers, where correct phasing is essential for accurate readings.

Practical example

Bij het in bedrijf stellen van een nieuwe energiemeter in een hoofdverdeelinrichting gebruikt de meettechnicus een fasorimeter om te controleren of de stroomtransformatoren met de juiste polariteit en fasehoek ten opzichte van de spanning zijn aangesloten, vóórdat de meter definitief wordt vrijgegeven.

Common mistake

Alleen de fasevolgorde controleren (draairichting correct) en aannemen dat de aansluiting daarmee volledig juist is, terwijl een stroomtransformator met omgekeerde polariteit dezelfde draairichting geeft maar wel een foutief vermogensteken en dus een verkeerde energiemeting oplevert.