IEC 60947-4-1

Contactor Utilization Category (AC-1, AC-3, AC-4)

Contactor-gebruikscategorie (AC-1, AC-3, AC-4)

A classification per IEC 60947-4-1 indicating the type of load and switching conditions a contactor or motor starter is designed and tested for, where each category prescribes a specific combination of making and breaking current (as a multiple of rated operational current) and switching frequency. AC-1 applies to non-inductive or slightly inductive loads (such as resistive heating), AC-3 to squirrel-cage motors with normal starting and stopping while running (the most common category for motor control), and AC-4 to squirrel-cage motors with jogging, reversing or plugging duty, where the contactor must switch under near-locked-rotor conditions and therefore withstands much more severe making/breaking conditions. Selecting a contactor based on rated current alone, without the correct utilization category, can lead to premature contact wear or welding.

Practical example

Voor het omkeren van een kooiankermotor in een hijsinstallatie selecteert de installateur een contactor met AC-4-classificatie in plaats van een goedkopere AC-3-contactor, omdat het omkeerbedrijf zwaardere schakelcondities met zich meebrengt.

Common mistake

Een AC-3-contactor toepassen in een toepassing met frequent jog-bedrijf of omkeren (die eigenlijk AC-4 vereist), waardoor de contacten sneller verslijten of zelfs vastlassen dan de fabrikant voor die toepassing garandeert.